Parameters accessible with Function Codes 04
January 09 UDA2182 Communications User Guide 33
Address
(hex)
Register
(decimal)
Parameter Name Type Notes
005A 30091
Input 1 Pharmacopia Calculated limit
Value
Float Input 1 Conductivity
005C 30093
Input 1 Pharmacopia Percentage of Limit
Output
Float Input 1 Conductivity.
005E 30095
Input 1 Pharacopia Warning Alarm
Long Input 1 Conductivity. On if
calculated percent of limit exceeds
user congured warning value.
0060 30097
Input 1 Pharmacopia Limit Alarm
Long Input 1 Conductivity. On if input
uS/cm exceeds USP scheduled
limit value.
0062 30099
Input 1 US Pharmacopia uS / cm
monitored Value
Float Input 2 Conductivity
0064 30101
Input 1 US Pharamacopia Sensor
monitored Temperature Value
Float Input 2 Conductivity
0066 30103
Input 1 Pharmacopia Calculated limit
Value
Float Input 2 Conductivity
0068 30105
Input 1 Pharmacopia Percentage of Limit
Output
Float Input 2 Conductivity.
006A 30107
Input 1 Pharacopia Warning Alarm
Long Input 2 Conductivity. On if
calculated percent of limit exceeds
user congured warning value.
006C 30109
Input 1 Pharmacopia Limit Alarm
Long Input 2 Conductivity. On if input
uS/cm exceeds USP scheduled
limit value.
006E 30111
UDA control execution cycle time
Float In seconds. Typically 0.25
seconds.
0070 30113
Execution time
Float Time it takes to complete the
algorithm execution.
0072 30115
Peak execution time
Float Longest execution time
encountered.
0074 30117
Percent resource used
Float Fixed number that is the ratio of
memory available and memory
used for algorithm execution.
Usually equals 100%.
0076 30119
Stack resource
Float Diagnostic data indicating how
much stack is used.
0078 30121
Control 1 Alarm 1
Long PID Option Installed
007A 30123
Control 1 Alarm 2
Long PID Option Installed
007C 30125
Control 1 Alarm 2
Long PID Option Installed
007E 30127
Control 2 Alarm 2
Long PID Option Installed
0080 30129
Output 1 Fault
Long 0= no fault; 1= fault
0082 30131
Output 2 Fault
Long 0= no fault; 1= fault
0084 30133
Output 3 Fault
Long 0= no fault; 1= fault