Parameters accessible with Function Codes 04
January 09 UDA2182 Communications User Guide 35
Address
(hex)
Register
(decimal)
Parameter Name Type Notes
00C8 30201
Number of messages sent by main CPU
card to communication card via SPI link
that failed.
Long
00CA 30203
Number of messages sent by
communication card to main CPU card
via the SCI link.
Long
00CC 30205
Number of messages sent by
communication card to main CPU card
via the SCI link that failed.
Long
00CE 30207
Number of times the communication card
was commanded to reset.
Long
00D0 30209
Analog variable 1 operating value
Float
00D2 30211
Analog variable 2 operating value
Float
00D4 30213
Analog variable 3 operating value
Float
00D6 30215
Analog variable 4 operating value
Float
00D8 30217
Digital variable 1 operating value
Long
00DA 30219
Digital variable 2 operating value
Long
00DC 30221
Digital variable 3 operating value
Long
00DE 30223
Digital variable 4 operating value
Long
00E0 30225
Number of times the database was
changed.
Long
00E2 30227
Number of times a tagname was
changed.
Long
00E3-
00FF
30228-30229
spare
0100 30257
PID1 LSP/RSP selected
Long 0 = LSP; 1 = RSP
0102 30259
PID1 AUTO/MANUAL selected
Long 0 = auto mode; 1 = manual mode
0104 30261
PID1 Tune request active
Long 1 = Auto tune is requested
0106 30263
PID1 RSP
Float RSP in engineering units
0108 30265
PID1 Deviation
Float Deviation in engineering units
010A 30267
PID1 Tuneset selected
Long 0 = tuneset 1; 1 = tuneset 2
010C 30269
PID1 PV
Float PV in engineering units
010E 30271
PID1 Working setpoint
Float Working setpoint in engineering
units
0110 30273
PID1 Output
Float PID output