Parameters accessible with Function Codes 04 
36  UDA2182 Communications User Guide  January 09   
Address 
(hex) 
Register 
(decimal) 
Parameter Name  Type  Notes 
0112 30275 
PID1 Mode 
Float  PID mode encoded as floating 
point number: 
0.0 = RSP/Auto 
1.0 = RSP/Manual 
2.0 = RSP/Initializing manual 
mode 
3.0 = RSP/TRC 
4.0 = LSP/Auto 
5.0 = LSP/Manual 
6.0 = LSP/ Initializing manual 
mode 
7.0 = LSP/TRC 
0114 30277 
PID1 Alarm 1 state 
Long  0 = PID alarm 1 inactive  
1 = PID alarm 1 active 
0116 30279 
PID1 Alarm 2 state 
Long  0 = PID alarm 2 inactive  
1 = PID alarm 2 active 
0118 30281 
PID1 Auto tune state 
Long  0 = auto tune inactive 
1 = auto tune active 
 011A  30283 
spare 
 
011C 30285 
spare
 
 
011E 30287 
spare
 
 
0120 30289 
PID2 LSP/RSP selected 
Long  0 = LSP; 1 = RSP 
0122 30291 
PID2 AUTO/MANUAL selected 
Long  0 = auto mode; 1 = manual mode 
0124 30293 
PID2 Tune request active 
Long  1 = Auto tune is requested 
0126 30295 
PID2 RSP 
Float  RSP in engineering units 
0128 30297 
PID2 Deviation 
Float  Deviation in engineering units 
012A 30299 
PID2 Tuneset selected 
Long  0 = tuneset 1; 1 = tuneset 2 
012C 30301 
PID2 PV 
Float  PV in engineering units 
012E 30303 
PID2 Working setpoint 
Float  Working setpoint in engineering 
units 
0130 30305 
PID2 Output 
Float PID output 
0132 30307 
PID2 Mode 
Float  PID mode encoded as floating 
point number: 
0.0 = RSP/Auto 
1.0 = RSP/Manual 
2.0 = RSP/Initializing manual 
mode 
3.0 = RSP/TRC 
4.0 = LSP/Auto 
5.0 = LSP/Manual 
6.0 = LSP/ Initializing manual 
mode 
7.0 = LSP/TRC 
0134 30309 
PID2 Alarm 1 state 
Long  0 = PID alarm 1 inactive  
1 = PID alarm 1 active