EasyManua.ls Logo

Honeywell VISTA-128BPT - Accessing Other Partitions

Honeywell VISTA-128BPT
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
3-6
Compatible Alarm Indicating Devices
Model Number Device Type Polarizing Diode
719 Compact Outdoor Siren(not UL Listed) Yes
747 Indoor Siren Yes
AB12M Bell Yes
System Sensor HR Fire Piezo Horn No
System Sensor P2RK, P4RK Fire Horn/Strobe No
Wheelock AS-121575W Fire Horn/Strobe No
ALARM SOUNDER OUTPUT:
1-VDC - 13.8VDC
1.7A MAXIMUM
BELL
HORN
7
6
+
-
+
-
8
3
1
2
4
fire_devices-001-V0
5
Figure 3-6: Wiring Polarized Fire Devices
PANEL BELL
PANEL BELL
TO
OTHER
DEVICES
NONPOLARIZED BURGLARY
INDICATING DEVICES
POLARIZED FIRE
INDICATING DEVICE
POLARIZING DIODES
(MUST MOUNT AT INDICATING DEVICE)
BELL
BELL
HORN
non_polar_devices
Figure 3-7: Wiring Nonpolarized Burglary Devices
Supervising the Alarm Output
To wire the alarm output using the supervision feature, perform the following steps:
Step Action
1 Wire polarized fire-indicating devices to the alarm output as shown in Figure 3-6.
2 Wire nonpolarized burglary indicating devices to the alarm output using a polarizing diode (two 2A diodes
supplied), as shown in Figure 3-7.
3 Program Zone 970 with a response type of 05 (trouble by day/alarm by night).
NOTE: When supervising the bell output (zone 970), only one device can be connected to the alarm output
(terminals 4 and 5) for UL and Fire installations.

Table of Contents

Other manuals for Honeywell VISTA-128BPT

Related product manuals