A-1
A P P E N D I X A
Regulatory Agency Statements
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
UL Installation Requirements
The following requirements apply to both UL Residential and UL Commercial Burglary installations:
• All partitions must be owned and managed by the same person(s).
• All partitions must be part of one building at one street address.
• The audible alarm device(s) must be placed where it/they can be heard by all partitions.
• The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the
cabinet door (not supplied with VISTA-128BPT/VISTA-250BPT) or by installing a UL Listed passive infrared detector
positioned to detect cabinet access. Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone
for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be
used for multiple-partitioned systems.
• Remote downloading and auto-disarming are not UL Listed features.
NOTE: UL Commercial Burglary installations require the attack resistant cabinet. The cabinet is included in the VISTA-
ULKT kit.
UL609 Local Mercantile Premises/Local Mercantile Safe & Vault
Use the following guidelines for a Local Mercantile Premises/Local Mercantile Safe & Vault installation:
• All zones must be configured for EOLR supervision (∗41=0). Wireless sensors may not be used. If 4190WH V-Plexs are
used set field ∗24 to “0” to enable tamper detection.
• Attach a door tamper switch (supplied) to the VISTA-128BPT/VISTA-250BPT cabinet backbox. For safe and vault
installations, a shock sensor (not supplied) must also be attached to the backbox. (Also see SECTION 3: Installing the
Control)
• Wire an ADEMCO AB12M Bell/Box to the bell output. Bell wires must be run in conduit. Program the bell output for a
timeout of 16 minutes or longer timeout and for confirmation of arming ding. (Also see SECTION 3: Installing the Control.)
• Wire the VISTA-128BPT/VISTA-250BPT tamper switch and AB12M Bell/Box tamper switches to any EOLR-supervised
zone (zones 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The
24-hour alarm response must be used for multiple-partitioned systems.
• Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.
UL365/UL609 Bank Safe and Vault Alarm System
• Follow the instructions for UL609 local installations above and Bank/Mercantile Safe and Vault (page 3-2) sections of this
manual.
• Bell 1 Confirmation of Arming Ding (∗16) must be set to 1 to on (enabled) (will automatically test bell).
• Entry delays or any other delays to report alarms may not exceed 45 seconds.
• Models 7847i, 7847i-E, IGSMV, and IGSMHS
• Bell Timeout must be programmed for 16 minutes min. (See Section 5, page 5-2)
• Two 17.2AH Batteries must be used for this application.
• The main protective circuits, linings and attachments on the safe and vault, control units and alarm housing must be of the
normally closed circuit, fully supervised type.
• To be installed inside the safe or vault.
UL365 Police Station Connected Burglar Alarm
Follow the instructions for UL609 local installations given above.
For Systems without Line Security:
• You may use the VISTA-128BPT/VISTA-250BPT dialer alone, or the 7847i Communicator alone.
• When using the dialer, program it to send Burglary Alarm, Low Battery, and Communicator Test reports. Field ∗27 must
be set to “0024” (or less).
• If you are using the 7847i Communicator, connect it to the VISTA-128BPT/VISTA-250BPT burglary/audible panic alarm
trigger.