SIA CP-01 Quick Reference Chart
The minimum required system for SIA CP-01 is a VISTA-128BPTSIA Control, one of the following keypad
models; 6160, TUXS, TUXW, 6280S, or 6280W and a UL Listed Bell.
Item Feature Range Shipping
Default
SIA
Requirement*
∗09
Entry Delay # 1
02 – 15 multiplied by 15
seconds
00 = 240 sec (4 minutes)
30 Seconds` At least 30 Seconds **
∗10
Exit Delay #1
03 – 15 multiplied by 15
seconds
60 Seconds 60 Seconds
∗11
Entry Delay # 2
02 – 15 multiplied by 15
seconds
00 = 240 sec (4 minutes)
30 Seconds At least 30 Seconds **
∗12
Exit Delay #2
03 – 15 multiplied by 15
seconds
60 Seconds 60 Seconds
∗28
Power Up in Previous
State
0 = no
1 = yes
Yes Yes
∗57
Dynamic Signaling
Priority
0 = primary dialer
1 = Communicator as
first reporting destination
0 (primary dialer) 0 (primary dialer)
∗84
Swinger Suppression 01-06 = 1–6 alarms 2 alarms 1 alarm
∗88
Abort Window Time
(for non-fire zones)
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
30 Seconds At least 15 Seconds **
1∗21
Exit Time Reset 0 = no
1 = Resets Exit Delay to
programmed value after
zone is closed and then
faulted prior to end of
exit delay.
1 (Enabled) 1 (Enabled)
1∗22 – 1∗25
Cross Zoning Zone 001 – 250
000, 000 = Disabled
Disabled
Enabled and two (or
more) zones
programmed
1∗42
Call Waiting Defeat 0 = no
1 = yes
Disabled (0)
Enabled if user has
call waiting
1∗61
Abort Verify 0 = Disable
1 = Enable
Enabled Enabled
Zone
Programming
Auto Stay
Zone, Zone
type 04 has
this feature
enabled by
default
Auto Stay Arm or
Occupied Premises
0 = Disable
1 = Enable
1 (Enabled) Enabled