Section 5 – Data Field Descriptions
5-9
FIELD
TITLE and DATA ENTRIES EXPLANATION
1
34
Communicator Split Reporting
0 = Split Reporting disabled
1 = Alarm, Alarm Restore, and Cancel
reports to primary, all others to secondary
2 = Open/Close and Test reports to
secondary, all other reports to primary
Select the type of split reporting for system communication.
NOTE: See 51 for split/dual reporting combinations.
NOTE: Split reporting should not be used with Dynamic Signaling.
1
35
Access Control Dialer Enables
0 = disable
1 = enable
There are six entries for this field as follows: Trace, Trouble, Not Used,
Bypass, System and Alarm.
If Trace is enabled, access grant/denial events sent to the central station.
For the other events, if enabled, a report is sent to the central station.
1
42
Call Waiting Defeat
0 = disable
1 = enable
If enabled, the system defeats Call Waiting on the first outgoing call attempt to
both the primary and secondary numbers.
NOTES:
After the panel's initial call to report the alarm, the panel may attempt to make
an additional call, perhaps for a cancel or a zone restoral. If Call Waiting is
not defeated, an operator at the central station attempting to contact the
premises (to verify whether the alarm is valid) hears the phone ringing
indefinitely and must to dispatch on the call.
DO NOT enable this feature unless Call Waiting is being used.
1
43
Permanent Keypad Display
Backlighting (partition-specific)
0 = disable
1 = enable
If enabled, backlighting for the keypad display remains on at all times.
Otherwise the backlighting comes on when a key is pressed.
NOTE: When a key is pressed, display backlighting turns on for all keypads in
that partition.
NOTE: This field affects only standard keypads, not graphic/touch-screen
keypads.
1
44
Wireless Keypad Tamper Detect
0 = disable
1 = enable
If enabled, when more than 40 key depressions are received without a valid
sequence (arm, disarm, etc.), the control panel disables the wireless keypad.
The inhibit is removed once a valid key sequence is received from a wired
keypad.
U
L
Wireless Keypad is not suitable for use in a UL
installation.
1
45
Exit Delay Sounding (partition-
specific)
0 = disable
1 = enable
If enabled, the system produces slow beeping from the keypads during exit
delay and reverts to rapid beeping during the last 10 seconds of the exit delay.
NOTES:
Must be set to “1” for UL/ULC installations.
The duration of the beeping is the programmed value of field 10 regardless
of which entry/exit zone is used to exit the premises.
See page 30 in the Programming Guide, “SOUND OPTION”, prompt for
disabling the entry/exit beeps on individual keypads.
1
46
Auxiliary Output Mode
0 = Not used
1 = smoke detector reset.
2 = Not used
3 = AAV module.
Select the mode for output 1 on the J7 triggers.
NOTES:
Only one of the options may be active within the system.
1
47
Chime On Ext. Siren (partition-
specific)
0 = disable
1 = enable
If enabled, the system produces chime annunciation on the external alarm
sounder.
1
48
Wireless Keypad Assignment
0 = none
1-8 = partition number
Select the partition in which RF keypad is used.
U
L
Wireless Keypad is not suitable for use in a UL
installation.