Section 5 – Data Field Descriptions
5-5
FIELD
TITLE and DATA ENTRIES EXPLANATION
45
Primary Format
1 = Contact ID; 2 = 10-Digit Contact ID; 3 =
4+2 Express
Enter the reporting format for the primary telephone number.
47
Secondary Format
1 = Contact ID; 2 = 10-Digit Contact ID; 3 =
4+2 Express
Enter the reporting format for the secondary telephone number.
51
Dual Reporting
0 = disable
1 = enable
If enabled, all reports are to be sent to both primary and secondary phone
numbers.
NOTE: If used with Split Reporting option 1 (134), alarms go to both primary
and secondary numbers, while all other reports go to secondary only. If used
with Split Reporting option 2, alarms go to both lines, open/close and test
messages go to secondary only, while all other reports go to primary.
56
Dynamic Signaling Delay
Enter 00-15 times 15 seconds.
Select the time the panel should wait for acknowledgment from the first
reporting destination before it attempts to send a message to the second
destination (first and second destinations are determined in field
57).
NOTE: If the acknowledgment is received before the delay time expires, no
message is sent to the second destination.
57
Dynamic Signaling Priority
0 = Primary Dialer
1 = Long Range Radio
Select the initial reporting path for central station messages.
58
Long Range Radio Central
Station #1 Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System and Test. If enabled, the reports are sent to the primary subscriber ID
of the Communicator.
59
Long Range Radio Central
Station #2 Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System and Test. If enabled, the reports are sent to the secondary subscriber
ID of the Communicator.
79
Zone Type Restores for Zone
Types 1-8
0 = disable
1 = enable
This field has eight entries, one for each zone type. Select the zone types that
will send Restore reports.
80
Zone Type Restores for Zone
Types 9, 10, 16 and 14
0 = disable
1 = enable
This field has four entries, one for each zone type. Select the zone types that
will send Restore reports.
83
First Test Report Time
Enter 00-07 for the day (01 = Monday)
Enter 00-23 for the hour
Enter 00-59 for the minutes
Enter the day and time that the first Test report shall be transmitted. Enter 00
in all locations if the Test report is to be sent immediately upon exiting. Enter
00 in the day location if the report is to be sent at the next occurrence of the
time that is set.
84
Swinger Suppression (partition-
specific)
Enter 01-14.
Enter 00 for unlimited reports
This option limits the number of messages (alarms or troubles) sent for a
specific zone in an armed period.
Must be 00 for UL installations.
85
Enable Dialer Reports for Panics
& Duress (partition-specific)
0 = disable
1 = enable
This field has four entries as follows: Zone 995, 996, 999, Duress Enable for
each partition that the panics and duress reporting is desired.
NOTE: Non-zero report code must be assigned to zone 992 (duress) to
enable Duress reporting.
If you enable any of the panics to report, make sure field 22 is programmed
correctly for each partition.