VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
4-2
In either of the above cases, simply re-enter [] + the
correct field number and then enter the correct data.
Programming System-Wide Data Fields
Values for some programming fields are system-wide
(global), and some can be different for each partition
(partition-specific).
The partition
-
specific programming fields are
automatically skipped when programming the
global fields. If the system has only 1 partition,
the partition-specific fields are not
automatically
skipped.
To program system-wide data fields, perform the
following steps:
Step Action
1 Enter Program Mode: Installer Code + 8 0 0 0.
The following display appears:
Program Mode
Fill # View – 00
2 If the control has not been programmed before,
enter 97 to load factory defaults.
3
Press [] and enter the first field number to be
programmed (for example, 00, Installers
Code). Make the desired entry. When the field
is complete, the keypad beeps three times and
advances to the next field. If you do not want to
change the next field, press [] and enter the
next field number to be programmed.
First Page of fields
(00 - 90)
To change to the next page of fields, press 94.
To return to the previous page of fields, press
99.
4
Press 99 or 98 to exit Program Mode.
NOTE: If the number of digits that you enter in a data
field is fewer than the maximum permitted (for
example, a phone number), the keypad displays the last
entry and waits. To proceed, enter [] + the next data
field you wish to program.
Programming Partition-Specific Data Fields
To program partition-specific data fields once in
Program Mode, do the following:
Step Action
1 Enter Program Mode: Installer Code + 8 0 0
0.
2
Press 91, which will prompt you for the
partition number desired.
3 Enter a partition-specific field number (e.g.,
09) to begin programming.
When the first field’s entry is completed, the
next partition-specific field is automatically
displayed. When all partition-specific fields
are programmed, the system returns to the
global programming fields (page 1 fields).
4 Repeat this procedure for each partition in
the installation.
NOTE: To return to the global program fields before
finishing all fields, enter any global field number.
Programming Partition-Specific Fields
Press 91 to select a partition.
Enter the partition to be programmed.
Enter a partition-specific field number and make entry.
After partition-specific fields are programmed,
press 91 to select next partition.
Enter any global field number to return to the global
fields at any time.
#93 Menu Mode Programming
The #93 Menu Mode is an interactive mode through which much of the system’s programming is done. In this mode,
there are “question and answer” prompts that can be accessed once Data Field Program Mode has been entered. These
prompts require a 2-line alpha keypad (6160).
After programming all system-related programming fields in the usual way, press #93 while still in programming mode
to display the first choice of the menu-driven programming functions. Press 0 (NO) or 1 (YES) in response to the
displayed menu selection. Pressing 0 will display the next choice in sequence.