Section 5 – Data Field Descriptions
5-11
FIELD
TITLE and DATA ENTRIES EXPLANATION
1
76
Access Control Relay (partition-
specific)
01-96 = relay number
00 = relay not used.
If enabled, the assigned relay closes for 2 seconds when the user enters his
code and presses 0.
Must be 00 for UL installations.
1
77
Log 1
st
Main Signal
0 = disable
1 = enable
If enabled, the system logs the first maintenance signal from each smoke
detector. If disabled, no logging occurs.
1
78
Extended Home Control Enable
0 = limited
1 = extended
If extended, there are 255 commands to the home control command set. If
limited, there are 32 commands to the home control command set.
Home Control Automation is not allowed in UL installations.
1
79
Home Control Events
0 = disable
1 = enable
This field has five entries as follows: Alarm, Trouble, Bypass, Open/Close,
and System. Select the type of events (status reports) transmitted via the
RS232 output (TB4).
Home Control Automation is not allowed in UL installations.
1
80
Log Faults & Restores
0 = disable
1 = enable
When enabled automatically transfers zone fault/restore data of the RS232
output (TB4).
Home Control Automation is not allowed in UL installations.
2
00
Number of Partitions
Enter 1-8.
Enter the number of partitions used in the system.
2
01
Daylight Saving Time Start/End
Month
0 = disable
1 = enable
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user’s region.
Standard setting for U.S. is 03,11.
2
02
Daylight Saving Time Start/End
Weekend
0 = disable
1 = enable
Enter the start and end weekends for daylight saving time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last.
Standard setting for U.S. is 2,1.
2
03
ULC S304 Enable
0 = disable
1 = enable
If enable is selected, the following will happen: A 2-minute stabilization upon
power up – (zones scanning will be disabled when the panel is powered up for
2 minutes). Previous reporting will be enabled. Attempting to arm when there
is a faulted burglary zone will cause a 4-second long tone.
U
LC
The ULC S304 Enable must be set to “1” (enabled) for ULC
installations.
U
L
Fields 2*05 – 2*08 must be set to 0 for UL installations.
2
05
Auto-Arm Delay (partition-
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
This is the time between the end of the arming window and the start of auto-
arm warning time (field 206).
2
06
Auto-Arm Warning Period
(partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
This is the time that the user is warned by a keypad sounding and display to
exit the premises prior to auto arming of the system.