Piping Design "I" pipe - Dual Channel (FLX-020):
FLX-020 I-pipe network, Class C without In-line filter
Exhaust pipe of 10m (E), First hole at 5m (F), Last hole at 35m from the first hole (L1), 6 holes
…
2. Calculate nominal step between holes and hole position deviation form nominal
1. Verification of project constraints and determination of aspirator speed
3. Determination of necessary Sensitivity Level
and the hole diameters
S1 = L1 / ( Number of holes – 1 ) = 35 / 5 = 7 m (≥2.5m)
± 0.2*7m = ±1.4m
3
Example:
Required Rules
N Number of holes 6
See Table
E Exhaust pipe 10m
max 14 (See Table row B)
L1 Last hole 35m
F First hole with low speed
with high aspirator speed
5m 1 ÷ (26-10)
1 ÷ (30-10)
PL Pipe length with low speed
with high aspirator speed
10+5+35=50m ≤ 50 m
≤ 80 m
1
2
4
Aspirator speed, max 65m for H and 45m for L
A
- Maximum First Hole Distance (meters)
B - Maximum Exhaust Pipe Length (meters)
Alarm Level Class C with/without filter
Alarm Level Class B with/without filter
Alarm Level Class A without filter only
Drilled hole diameter (mm)
H1
6.5
H1
6
H1
5
H1
4
H1
4
H1
3
FAASTFLEX FAAST FLEX Product Guide
www.xtralis.com 58