EasyManuals Logo

Honeywell Xtralis FAAST FLEX FLX-020 User Manual

Honeywell Xtralis FAAST FLEX FLX-020
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
Piping Design "I" pipe - Dual Channel (FLX-020):
FLX-020 I-pipe network, Class C without In-line filter
Exhaust pipe of 10m (E), First hole at 5m (F), Last hole at 35m from the first hole (L1), 6 holes
2. Calculate nominal step between holes and hole position deviation form nominal
1. Verification of project constraints and determination of aspirator speed
3. Determination of necessary Sensitivity Level
and the hole diameters
S1 = L1 / ( Number of holes – 1 ) = 35 / 5 = 7 m (≥2.5m)
± 0.2*7m = ±1.4m
l
3
Example:
Required Rules
N Number of holes 6
See Table
E Exhaust pipe 10m
max 14 (See Table row B)
L1 Last hole 35m
F First hole with low speed
with high aspirator speed
5m 1 ÷ (26-10)
1 ÷ (30-10)
PL Pipe length with low speed
with high aspirator speed
10+5+35=50m ≤ 50 m
≤ 80 m
1
2
4
4
4
Number of Branch Holes
Aspirator speed, max 65m for H and 45m for L
A
- Maximum First Hole Distance (meters)
B - Maximum Exhaust Pipe Length (meters)
Alarm Level Class C with/without lter
Alarm Level Class B with/without lter
Alarm Level Class A without lter only
Drilled hole diameter (mm)
H1
6.5
H1
6
H1
5
H1
4
H1
4
H1
3
High
High
High
High
High
High
NN
30/30
30/30
30/30
30/30
30/26
Low
Low
Low
Medium
Medium
Medium
14/14
14/14
14/14
14/14
14/14
14/14
1
2
3
4
5
6
H/L
H/L
H/L
H/L
H/L
H/L
-
-
-
High
High
High
6
1
2
3
4
4
4
FAASTFLEX FAAST FLEX Product Guide
www.xtralis.com 58

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Xtralis FAAST FLEX FLX-020 and is the answer not in the manual?

Honeywell Xtralis FAAST FLEX FLX-020 Specifications

General IconGeneral
BrandHoneywell
ModelXtralis FAAST FLEX FLX-020
CategorySmoke Alarm
LanguageEnglish

Related product manuals