6.2 NORMAL Mode
This is normal working mode. The device monitors the power supply voltage, aspirator speed, smoke levels,
air flows, cover status, and signals and logs faults, actions, alarms.
6.3 WAIT Mode
The WAIT mode is a sub-mode of the NORMAL mode. There are two ways to enter into the WAIT mode:
1. If the cover is open the device enters WAIT mode after power-on and initialization.
2. If the cover is opened while the device is in NORMAL mode.
On entering WAIT Mode the POWER LED blinks yellow (slow blink). At this point the device is waiting for a
button press.
After 60 seconds of no activity in WAIT mode the device will automatically go into the SERVICE mode. Every
time an action (button or BLT) is performed in WAIT mode the timeout timer restarts. If a non-protected action
(no passcode required) is requested, the command is executed and then the device comes back to WAIT
mode. If a protected action (passcode required) is requested, user is prompted to enter the passcode. If the
passcode is correct the device will perform the requested action.
WAIT Mode Actions
Note: For a long press of a button, press and hold it for 5 seconds.
Table6-1: WAIT Mode Actions
Action Button LEDDisplay Description
Toggle button beeps ON/OFF
Short
Press
LED 6 will show green ON
for 3 seconds as feedback.
Default beeps ON.
Initiate NORMALIZE procedure
(Passcode Authentication
Required - if not authenticated,
you must enter the passcode to
start procedure.)
Long
Press
LEDs 1 through 4 will show
yellow to indicate that the
NORMALIZE procedure
has started. See section
6.3.4 Normalize.
Copy LOGREPOR.TXT to USB
drive
Short
Press
USB drive must be
inserted. See section 6.3.6
Event Logs for more
information.
Enter CHANGE CONFIGURATION
MODE
(Passcode Authentication
Required)
Long
Press
LEDs 1 through 4 will show
yellow to indicate change
configuration procedure has
started. See section 6.3.3
Changing Configuration
Mode.
Reset active Alarms or Faults
(Passcode Authentication
Required)
Short
Press
Resets the latched alarm
and faults status.
Toggles DISABLE Mode ON/OFF
(This option is NOT AVAILABLE
if GPI is disabled in extended
mode)
Long
Press
LEDs 1 through 4 will show
yellow to indicate disable
mode has turned ON/OFF.