FAAST FLEX Product Guide FAASTFLEX
32 www.xtralis.com
6.3.4 Normalize
Normalize procedure is used to set a new nominal flow reference based on the pipe network connected to
device, with this procedure the two thresholds for maximum and minimum flow are re-calculated and changed
according to the chosen tolerance.
Normalize procedure must be done during commissioning, when pipes are installed and drilled, to be sure that
the flow obtained is considered similar to the reference by FAAST FLEX that will update the flow tolerance
range accordingly with this value.
l If the flow is not normalized, the detector can report flow faults.
l If there is a change in the flow, we suggest checking if the are filters clean and pipeline’s integrity before
starting the normalization procedure.
Note: Before starting the NORMALIZE procedure, the pipe system should be connected and checked.
There can be no blockages, open pipes, dirty filters, dust, or other obstructions. The device should
be working for a minimum of 2 minutes and air flow must be stable.
Action Button LED Display Description
While the device is in
WAIT mode, long press
the SILENCE/+ button.
(Enter the current
passcode.)
Long
Press
1 3
2 4
5
6
LED 5 slow
b
link yellow
LED 6 will flash red
until the procedure is
complete.
Once the NORMALIZE
procedure is complete, the
buzzer will sound for 0.5
seconds. LED 6 will
indicate the result.
1 3
2 4
5
6
LED 5 slow
b
link yellow
LED 6 will show green
if the NORMALIZE
procedure completed
successfully.
1 3
2 4
5
6
LED 5 slow
b
link yellow
LED 6 will show red if
the NORMALIZE
procedure was
unsuccessful.
Unit will return to WAIT
mode.
Note: If the cover is closed during the NORMALIZE procedure, then the procedure is aborted and the
device will return to NORMAL mode.
6.3.5 Resetting Alarms and Faults
To reset any alarm and/or fault conditions press the RESET button. You will be prompted to enter the
passcode. Once the passcode has been successfully entered,all latched alarms and faults are reset (both
LEDs and relays) and the device returns to WAIT mode.