EasyManua.ls Logo

HORNER HE-XE1E2 - Figure 17.3 - Clone Unit Confirm Screen; Figure 17.4 - Clone Unit Files

Default Icon
158 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN0878-09-EN_XLE_XLT_UserManual
A u g u s t 2 3 , 2 0 1 8 P a g e 139 | 158
NOTE:
a. In Figure 17.2 above, F3 and F4 are inactive in the Clone Unit.
b. DSK when selected shows the number of total and free bytes in Removable Media.
3. Make/Create Clone option enables the user to duplicate / Clone an application file, all unit
settings and all register values from Battery Backed RAM.
Selecting Make Clone brings up the screen below:
XLT:
XLE:
Figure 17.3 Clone Unit Confirm Screen
After confirmation, the OCS will create two new files in the root directory of the Removable
Media Drive as shown below:
AUTOLOAD.PGM Application file
CLONE.DAT File having all unit settings and register values from Battery Backed RAM
XLT:
XLE:
Figure 17.4 Clone Unit Files
NOTE: Make/Create clone operation automatically includes the security in AUTOLOAD.PGM file