XLT/XLTe Modbus Table
Table 19.2 XLT/XLTe Modbus Master Mapping
XLT/XLTe
Reference
Maximum
Range
Trad.
Modbus Ref.
(5 digits)
Expanded
Modbus Ref.
(6 digits)
Modbus Command(s)
Modbus
Offset
%I1
2048
10001
010001
Read Input Status (2)
0
%IG1
64
13001
013001
3000
%S1
13
14001
014001
4000
%K1
4
15001
015001
5000
%Q1
2048
00001
000001
Read Coil Status (1)
Force Coil (5)
Force Multiple Coils (15)
0
%M1
2048
03001
003001
3000
%T1
2048
06001
006001
6000
%QG1
64
09001
009001
9000
%AI1
512
30001
030001
Read Input Register (4)
0
%AIG1
32
33001
033001
3000
%SR1
192
34001
034001
4000
%AQ1
512
40001
040001
Read Holding Register (3)
Load Register (6)
Load Multiple Registers (16)
0
%R1
2488
40513
040513
0
%R1
2048
43001
043001
3000
%AQG1
32
46001
046001
6000
%R1
9999
--
410001
10000

Table of Contents