MAN0878-09-EN_XLE_XLT_UserManual
A u g u s t 2 3 , 2 0 1 8 P a g e 52 | 158
View Status
The View Status Sub-Menu displays up to 17 System Settings. The Lcl Net Use % and All Net Use %
System Settings only appear for XLE/XLT models that have CAN ports (XE1xx). Only the Mode System
Setting is editable.
Model: XExyyz = 5 or 6 character Model number of this XLE/XLT unit
x is 1 for models that have a CAN port; 0 = no CAN port
yy indicates the installed I/O module; 00 = no I/O module
z indicates the installed COM module; N = no COM module
Mode: Idle = XLE/XLT is in Idle mode
DoIo = XLE/XLT is in Do I/O mode
Run = XLE/XLT is in Run mode
Scan Rate(mS): 0.0 = XLE/XLT is not in Run mode
0.1 to 999.9 = Average number of mS for each ladder scan
Lcl Net Use %: 0.0 to 100.0 = CAN network bandwidth % used by this XLE/XLT node
All Net Use %: 0.0 to 100.0 = CAN network bandwidth % used by all nodes
Ladder Size: x = Number of bytes in application ladder program
Config Size: x = Number of bytes in application I/O configuration
Graphics Sz: x = Number of bytes in application graphic screens
String Size: x = Number of bytes in application string table
Bitmap Size: x = Number of bytes in application bitmaps
Text Size: x = Number of bytes in application text tables
Font Size: x = Number of bytes in application font tables
Protocol Sz: x = Number of bytes in application downloaded protocols
SMS Msg Sz: x = Number of bytes in application SMS protocol configuration
Firmware Rev: xx.yy = Current firmware version
CPLD Rev: x.y = Current CPLD (Complex Programmable Logic Device) version
Self-Test: Ok = All power-on self-tests passed
Fault = One or more power-on self-tests failed