Cleanliness requirements
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal components and
contact points, especially when indoor relative humidity is low. In the worst case, electrostatic adsorption can cause
communication failure. The dust concentration limit s listed in Dust concentration limit in the equipment room.
Table 2: Dust concentration limit in the equipment room
Substance Concentration limit (particles/m
3
)
Dust ≤ 3 x 10
4
(no visible dust on the tabletop over three days)
NOTE: Dust diameter ≥ 5 μm
The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and premature aging of
components, as shown in Harmful gas limits in the equipment room.
Table 3: Harmful gas limits in the equipment room
Gas Chemical formula Maximum concentration (mg/m
3
)
Sulfur dioxide SO
2
02
Hydrogen sulfide H
2
S 0006
Ammonia NH
3
005
Chlorine Cl
2
001
EMI requirements
All electromagnetic interference (EMI) sources, from outside or inside of the switch and application system, adversely aect
the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE) to filter interference from
the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
Laser safety requirements
WARNING: Do not stare into any fiber port when the switch has power. The laser light emitted from the optical fiber
might hurt your eyes.
The switch is a Class 1 laser device.
Preparation for installation 9

Table of Contents

Other manuals for HPE 5920 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE 5920 series and is the answer not in the manual?

HPE 5920 series Specifications

General IconGeneral
BrandHPE
Model5920 series
CategorySwitch
LanguageEnglish

Related product manuals