b. Connect each power cord to the power source.
16. Power up the server.
ResultsResults
The installation is complete.
High performance heatsink optionHigh performance heatsink option
When a processor with a 260 W to 300 W TDP is installed, the high performance heatsink and high performance fans are both required.
SubtopicsSubtopics
Heatsink labelHeatsink label
Installing the high performance heatsinkInstalling the high performance heatsink
Heatsink labelHeatsink label
Before installing or removing a heatsink, review the information on the heatsink label:
Identify the correct sequence for:
Loosening the heatsink screws:
6-5-4-3-2-1
Tightening the heatsink screws:
1-2-3-4-5-6
Verify that the Front of ServerFront of Server arrow points to the front panel.