The arrow points to the front of the server.
Fan and heatsink requirementsFan and heatsink requirements
CAUTION:CAUTION: To maintain proper system cooling, install the correct fan and heatsink types required for specific hardware
configurations.
CAUTION:CAUTION: To maintain proper system cooling, when a 25 Gb or faster Ethernet / InfiniBand adapter / HPE Storage
Networking NVMe-oF Offload Adapter / HPE NS204i-u Boot Device / accelerator is installed in any configuration, make
sure to use high performance fans.
The system-operating temperature for most components installed in this server is at standard temperature ( 10°C to 35°C / 50°F to 95°F ).
However, system performance during standard operating support may be reduced if operating above 30°C (86°F). The following table
contains the allowed hardware configurations that the system can be run at 30°C (86°F) without system performance degradation.
4 LFF drive configurations4 LFF drive configurations
Processor TDPProcessor TDP Fan typeFan type Heatsink typeHeatsink type
≤ 240 W Standard fan Standard heatsink
≤ 240 W High performance heatsink
≤ 300 W High performance fan High performance heatsink
≤ 400 W Liquid cooling fan Liquid cooling heatsink
The maximum recommended ambient operating temperature is 27℃.
Option kit: P58461-B21
Option kit: P58456-B21
Option kit: P58457-B21
Option kit: P58462-B21
Option kit: P59668-B21
Option kit: P58463-B21
8 SFF drive configurations8 SFF drive configurations