Chapter 8 Maintenance Shenzhen Hpmont Technology Co., Ltd
112 HD20 Series Inverters User Manual
Table 8-1 Daily checking items
Items Content Criteria
Operating
environment
Temperature and humidity -10+40, derating at 4050
Dust and water dripping No water dripping
Gas No strange smell
Inverter
Oscillation and heating
Stable oscillation and proper
temperature
Noise No abnormal sound
Motor
Heating No overheating
Noise Low and regular noise
Operating status
parameters
Output current Within rated range
Output voltage Within rated range
8.2 Periodical Maintenance
Customer should check the inverter in short time or every 3 to 6 months according to the actual
environment so as to avoid hidden problems and make sure the inverter runs well for a long time.
General Inspection:
Check whether the screws of control terminals are loose. If so, tighten them with a screw
driver;
Check whether the main circuit terminals are properly connected; whether the mains cables
are over heated;
Check whether the power cables and control cables are damaged, check especially for any
wear on the cable tube;
Check whether the insulating tapes around the cable lugs are stripped, and for signs of
overheating near terminations;
Clean the dust on PCBs and air ducts with a vacuum cleaner;
Note:
1. Dielectric strength test of the inverter has already been conducted in the factory. Do not do the
test again. Otherwise, the inverter might be damaged.
2. If insulation test to the motor is necessary, it should be done after the motor’s input terminals U,
V, W have been detached from the inverter. Otherwise, the inverter will be damaged.
3. For inverters that have been stored for a long time, they must be powered up every 2 years.
When supplying AC power to the inverter, use a voltage regulator to gradually raise the input
voltage to rated input voltage at least 5 hours.