Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD20 Series Inverters User Manual 137
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
F15.06 Reserved
F15.07 Reserved
F15.08 Reserved
F15.09 Reserved
F15.10 Reserved
F15.11 Reserved
F15.12
Acc./Dec. rate of UP/DN
terminal
0.0099.99Hz/s 1.00Hz/s 0.01Hz/s ×
F15.13 Terminal detecting interval
0: 2ms
1: 4ms
2: 8ms
0 1
F15.14
Terminal detecting filter
number
010000 2 1
F15.15
Terminal input positive and
negative logic setting
Bit0Bit8 is corresponding to
DI1DI9
Bitx: DIy terminal input positive
and negative logic
0: Positive logic
1: Negative logic
00 1
F15.16 FWD/REV operation mode
0: Two-wire operation mode 1
1: Two-wire operation mode 2
2: Three-wire operation mode
1
3: Three-wire operation mode
2
0 1 ×
F15.17
Terminal operating
selection due to fault of
external equipment
0: Coast to stop
1: Emergency stop
2: Decelerate to stop
3: Continue to run
0 1 ×