Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd
76 HD20 Series Inverters User Manual
No. Name Description Range
factory setting
F13.12 Idling exciting current of motor 2 0.00
99.99A
dependent on
inverter model
F13.13
Reserved
F13.14 Reserved
F13.15
Reserved
F13.16 V/f curve selection of motor 2 0
4
0
0: Line.
1: Square curve.
2: 1.2 exponential curve.
3: 1.7 exponential curve.
4: User-defined curve.
F13.17 V/f frequency value F3 of motor 2 F13.19
F13.04
0.00Hz
F13.18
V/f voltage value V3 of motor 2
F13.20F13.020V
F13.19 V/f frequency value F2 of motor 2 F13.21
F13.17
0.00Hz
F13.20
V/f voltage value V2 of motor 2
F13.22F13.180V
F13.21 V/f frequency value F1 of motor 2 0.00
F13.19
0.00Hz
F13.22
V/f voltage value V1 of motor 2
0F13.200V
F13.23 Torque boost of motor 2 0.0
30.0
2.0%
F13.24
Cut-off point used for manual torque boost of motor 2
0.050.0 (F13.04)30.0%
F13.25 Slip compensation gain of motor 2 0.0
300.0
100.0%
F13.26
Slip compensation filter time of motor 2
0.0110.000.10s
F13.27 Slip compensation limitation of motor 2 0.0
250.0
200.0%
F13.28
Compensation constant of motor 2
0.125.02.0s
F13.29 Reserved
F13.30
AVR (automatic voltage regulation) function of motor 2
021
F13.31 Oscillation-suppression mode of motor 2 0,1
0
F13.32
Oscillation-suppression coefficient of motor 2
020050
F13.33 Reserved
F13.34
Reserved
F13.35 Speed control proportional gain 1 of motor 2 0.1
200.0
20.0
F13.36
Speed control integral time 1 of motor 2
0.0010.000.20s
F13.37 Speed control proportional gain 2 of motor 2 0.1
200.0
20.0
F13.38
Speed control integral time 2 of motor 2
0.0010.000.20s
F13.39 Speed-loop PI switching frequency 1 of motor 2 0.00
50.00
10.00Hz
F13.40
Speed-loop PI switching frequency 2 of motor 2
0.0050.0015.00Hz
F13.41 Speed-loop integral limitation of motor 2 0.0
200.0 (F13.03)
180.0%
F13.42
Speed-loop differential time of motor 2
0.001.000.00s
F13.43 Speed-loop output filter time of motor 2 0.000
1.000
0.020s
F13.44
Reserved
F13.45 Reserved
F13.46
Motor torque limitation when motor 2 is forward
0.0
200.0 (F13.03)
180.0%
F13.47 Motor torque limitation when motor 2 is reverse
F13.48
Recreated torque limitation when motor 2 is forward
F13.49 Recreated torque limitation when motor 2 is reverse
F13.50
Reserved

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont HD20 Series and is the answer not in the manual?

hpmont HD20 Series Specifications

General IconGeneral
Brandhpmont
ModelHD20 Series
CategoryInverter
LanguageEnglish

Related product manuals