Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd
―66― HD5L Series Controller User Manual
Code Name Description Range
factory setting
F05.12 FDT1 0.0
100.0 (F00.02)
90.0%
0.0-100.0 (F00.02)【90.0%】
F05.14 FDT1 delay level 0.0
100.0 (F00.02)
1.0%
When running speed is lower than one speed
(F05.12 + F05.14) as figure’s FL, ON indicating
signal will be output till the running speed is lower
than F05.12.
• Refer to parameter F05.12 and F05.14 about
F05.13 and F05.15.
The pulse signal will be output if the controller’s
output frequency is within the FAR range. As
shown in the right figure.
80.0-120.0(F00.02)【115.0%】
F05.18 Over-speed detection time 0.0
2.0s
0.2
When the elevator actual speed exceeds F05.17 setting value and the duration time exceeds F05.18
setting value, the controller alarms E0032 fault (motor over speed).
• Set F05.18 as 0, the controller does not detect motor over speed fault.
F05.19 Detected value of speed deviation 0.0
30.0(F00.02)
20.0%
Detected time of speed deviation
When the deviation of setting speed (after Acc/Dec) and motor actual run speed exceeds F05.19
setting value and the duration time exceeds F05.20 setting value, the controller alarms E0018 fault
(excessive speed deviation).
• Set F05.19 or F05.20 as 0, the controller does not detect the excessive speed deviation fault of
motor.
F05.22 Creeping speed 0.000
0.400
0.050m/s
It defines the running speed at the forced Dec run.
F05.23
F05.25 Reserved
F05.14
F05.12
FL
DO
ON ONOFF
FL = F05.12 + F05.14
Elevator speed
Time
Time
Elevator
speed
F05.16
Refernece
speed
Time
Time
DO