Conguration N+X-
Norma
l
Temp-
CE
N+X-
Low
Temp-
CE
2N-
Norma
l
Temp-
CE
2N-
Low
Temp-
CE
N+X-
Norma
l
Temp-
CCC
N+X
Low
Temp-
CCC
2N-
Norma
l
Temp-
CCC
2N-
Low
Temp-
CCC
Backup
time
(lead-
acid
battery)
7 minutes
Backup
time
(lithium
battery)
25 minutes
Power
density
Total power ≤ 54
kW
6 kW/R: 6 PCS
9 kW/R: 2 PCS
Total power ≤ 54
kW
9 kW/R: 6 PCS
Total power ≤ 54
kW
6 kW/R: 6 PCS
9 kW/R: 2 PCS
Total power ≤ 54
kW
9 kW/R: 6 PCS
Environm
ent
corrosion
requirem
ents
Class A, B, or C environment. Class C environments are more than 500 m
away from strong-corrosion environments (seas, garbage dump areas, and
heavy pollution sources, such as a chemical factory).
NOTICE
Class C environments are not supported at a temperature ranging from –40°C to –
20°C.
Quakepro
of level
Complies with GR-63-CORE Zone 3.
Salt spray
corrosion
resistance
The pre-fab. module surface is sprayed with special coating and passes the
1440-hour salt spray test by UL.
Storage
temperat
ure range
–40°C to +70°C [not applicable to batteries (0°C to 40°C) and PADs (–20°C
to +45°C)
Storage
humidity
range
5%–95% RH
Structu
ral
system
Weight Preinstallation weight before delivery: ≤ 14 T; full conguration with
equipment: ≤ 20 T
Aisle
width
Long aisle: 640 mm; cold aisle: 1150 mm; hot aisle: ≥ 510 mm
Cabinet
type
The battery cabinet can slide 200 mm in both directions. Other cabinets are
xed.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
2 Typical Application Scenarios and Typical
Conguration
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 6