Conguration N+X-
Norma
l
Temp-
CE
N+X-
Low
Temp-
CE
2N-
Norma
l
Temp-
CE
2N-
Low
Temp-
CE
N+X-
Norma
l
Temp-
CCC
N+X
Low
Temp-
CCC
2N-
Norma
l
Temp-
CCC
2N-
Low
Temp-
CCC
Power
supply
and
distribu
tion
system
Power
system
380 V/400 V/415 V, 50/60 Hz; three-phase four-wire + PE
Input
voltage
range
380/400 V (tolerance: ±15%), 415 V (tolerance: +10%)
Number
of inputs
Two inputs
Input
current
250 A
Model
and
number
of UPSs
UPS5000-E, 1
PCS
UPS5000-E, 2
PCS (1+1
system)
UPS5000-E, 1
PCS
UPS5000-E, 2
PCS (1+1
system)
Power
capacity
≤ 60 kVA
(module 2+1
redundancy)
≤ 60 kVA
(module 2+0
redundancy)
≤ 60 kVA
(module 2+1
redundancy)
≤ 60 kVA
(module 2+0
redundancy)
Total
input
surge
protectio
n
Class B, 8/20 µs, I
n
= 30 kA, I
max
= 60 kA
Battery
specicati
ons
SmartLi lithium
battery cabinet
(half-capacity
cabinet 76 Ah,
six battery
modules in one
string) x 1
SmartLi lithium
battery cabinet
(half-capacity
cabinet 760 Ah,
six battery
modules in one
string) x 2
SmartLi lithium
battery cabinet
(half-capacity
cabinet 76 Ah,
six battery
modules in one
string) x 1
SmartLi lithium
battery cabinet
(half-capacity
cabinet 76 Ah,
six battery
modules in one
string) x 2
Lead-acid
battery pack (12
V/9 Ah) x 8
Lead-acid
battery pack (12
V/9 Ah) x 16
Lead-acid
battery pack (12
V/9 Ah) x 8
Lead-acid
battery pack (12
V/9 Ah) x 16
rPDU
type
IEC standard CCC standard
Cooling
system
Cooling
capacity
25 kW @ 37°C, 20% RH/35°C
Redunda
nt
congura
tion
3+1 redundancy
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
2 Typical Application Scenarios and Typical
Conguration
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 7

Table of Contents

Other manuals for Huawei FusionDC1000A

Related product manuals