No. Cable Type Conductor
Cross-
Sectional Area
Range
Outer
Diameter
Source
2 AC output
power cable
● If you connect a ground
cable to the ground
point on the chassis
shell, you are advised to
use a three-core (L1, L2,
and L3) outdoor cable
and M10 OT/DT
terminals (L1, L2, and
L3).
● If you connect a ground
cable to the ground
point in the
maintenance
compartment, you are
advised to use a four-
core (L1, L2, L3, and PE)
outdoor cable, M10
OT/DT terminals (L1, L2,
and L3), and M8 OT/DT
terminals (PE). You do
not need to separately
prepare a PE cable.
● Copper-core
cable:
– L1, L2,
L3: 25–
95 mm
2
– PE: ≥ 16
mm
2
. For
details,
see
Table
5-3.
● Aluminum
alloy cable
or copper-
clad
aluminum
cable:
– L1, L2,
L3: 35–
95mm
2
– PE: ≥ 16
mm
2
. For
details,
see
Table
5-3.
24–57 mm Prepared
by the
custome
r
3 Tracking system
power cable
Three-core outdoor copper
cable with dual-layer
protection
6 mm
2
14–18 mm Prepared
by the
custome
r
4 DC
input
power
cable
Amph
enol
UTX
PV
Conne
ctors
PV cable that meets the
1500 V standard
4–6 mm
2
(12–
10 AWG)
4.5–7.8 mm Prepared
by the
custome
r
MC4
EVO2
PV
Conne
ctors
4–6 mm
2
(12–
10 AWG)
4.7–6.4 mm Prepared
by the
custome
r
SUN2000-(90KTL, 95KTL, 100KTL, 105KTL) Series
User Manual
5 Electrical Connections