5.8 (Optional) Installing the Power Cable of the
Tracking System
Precautions
The tracking system should be equipped with an overcurrent protective device/
component. The power cable between the device/component and wiring terminal
should be no longer than 2.5 m.
● The tracking system is powered by the three-phase AC power grid with a rated
voltage of 800 V.
● Keep inammable materials away from the power cable.
● The power cable must be protected with a conduit to prevent short circuits
caused by insulation layer damage.
● If there is a power port for the tracking system in the maintenance
compartment of the inverter, connect the power cable of the tracking system
to the power port.
● If there is no power port, connect the power cable to the AC terminal block.
Connecting the Power Cable to the Power Port for the Tracking System
Step 1 Remove the sealing nut from the cable gland.
Step 2 Prepare a cable.
Step 3 Route the cable through the cable gland.
Step 4 Connect the power cable of the tracking system.
Step 5 Bind the power cable of the tracking system.
Step 6 Tighten the cable gland.
SUN2000-(90KTL, 95KTL, 100KTL, 105KTL) Series
User Manual
5 Electrical Connections
Issue 11 (2020-08-30) Copyright © Huawei Technologies Co., Ltd. 62