Note: The I/O backplane and the SPCN connector card are replaced as a pair.
6. Reinstall the RIO bus adapter card. (See “D10 RIO Bus Adapter” on page 121).
7. Reinstall the power supplies. (See “D10 Power Supply”).
8. Reinstall the cover. (See “D10 Covers” on page 59).
9. Reinstall all PCI adapters. (See “D10 PCI Adapters” on page 61).
10. Return the I/O subsystem to the operating position (see “D10 Operating Position”
on page 57) and connect RIO, SPCN, and adapter cables.
11. Connect the power cables.
12. Power the system on.
D10 Power Supply
Before performing the following procedure, read the “Safety Considerations” on
page 53.
Removal
Attention: Do not remove two power supplies at the same time if performing hot-plug
procedures. Power supplies are considered as hot-pluggable FRUs only if you remove
one power supply at a time. The power supplies can be removed from the front of the
I/O subsystem.
1. Disconnect the power cord from the power supply.
2. Unlatch the power supply handle and rotate the handle downward to unseat the
power supply.
Attention: Do not remove a power supply for more than four minutes. If you
cannot replace the power supply in less than four minutes, shut down the system
and then remove the power supply.
3. Pull the power supply straight out from the I/O subsystem.
Replacement
To replace the power supply, perform the steps in the removal procedure in reverse
order.
Chapter 8. Removal and Replacement Procedures 123