Table 5. SPCN Error Codes (continued)
Error Code Description Action/
Possible Failing FRU
1011 1912 Power supply 1 non-power fault 1. CEC drawer power supply 1
Location: U1.1-V1
2. Primary I/O backplane
Location: U0.1-P1
1011 1913 Power supply 1 domain fault 1. CEC drawer power supply 1
Location: U1.1-V1
2. Primary I/O backplane
Location: U0.1-P1
1011 1914 Power supply 1 cooling fault 1. CEC drawer power supply 1
Location: U1.1-V1
2. Primary I/O backplane
Location: U0.1-P1
1011 1920 Power supply 2 power source failure 1. Check input power to Power Supply 2
Location: U1.1-V2
2. CEC drawer power supply 2
Location: U1.1-V2
3. Primary I/O backplane
Location: U0.1-P1
1011 1921 Power supply 2 fault 1. CEC drawer power supply 2
Location: U1.1-V2
2. Primary I/O backplane
Location: U0.1-P1
1011 1922 Power supply 2 non-power fault 1. CEC drawer power supply 2
Location: U1.1-V2
2. Primary I/O backplane
Location: U0.1-P1
1011 1923 Power supply 2 domain fault 1. CEC drawer power supply 2
Location: U1.1-V2
2. Primary I/O backplane
Location: U0.1-P1
1011 1924 Power supply 2 cooling fault 1. CEC drawer power supply 2
Location: U1.1-V2
2. Primary I/O backplane
Location: U0.1-P1
1011 1926 Power supply 2 missing CEC drawer power supply 2
Location: U1.1-V2
1011 1B01 Load fault on +12V 1. I/O drawer power supply
Location: U0.1-V1
2. If power supply U0.1-V2 present (no
cooling unit), use the power supply you
removed from U0.1-V1 to replace
U0.1-V2
3. Primary I/O backplane
Location: U0.1-P1
1011 1B02 Load fault on +5V 1. I/O drawer power supply
Location: U0.1-V1
2. If power supply U0.1-V2 present (no
cooling unit), use the power supply you
removed from U0.1-V1 to replace
U0.1-V2
3. Primary I/O backplane
Location: U0.1-P1
Chapter 5. Error Code to FRU Index 167