17
INSTALLATION
Ideal Logic Code Combi - Installation and Servicing

Notes.
1. It is recommended that a support bracket
is tted for every 1 metre of extension pipe
used and a bracket should be used at every
joint, to ensure pipes are held at the correct
angle.
If a slip joint coupling is to be used then a
bracket should be used to secure the collar.
2. When extension ‘D’ packs are used the ue
duct MUST be inclined at 1.5 degrees to
the horizontal to allow condensate to drain
back into the boiler and out through the
condensate drain.
3. If the B pack, or telescopic B pack only are
used, they may be mounted horizontally.
The 1.5 degrees is taken care of by the
inclination of the ue within the air pipe.
4. Only use water as a lubricant during
assembly.
11
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED CONT’D
12
FLUE ASSEMBLY - Exploded View

kit is required for wall
thicknesses greater than :
Side 
Rear 420mm

LEGEND
1. 
2. 
3. 


uppermost to allow the

the plume management


Total Flue Length Dimension

Flue




Extra packs
required

  none 
   
Up to 2540 mm Up to 2540 mm  
   
Up to 4440 mm Up to 4440 mm  
   
   
   
   
   
Total Flue Length Dimension

Flue




Extra packs
required

Up to 575 mm Up to 575 mm none 
Up to 1525 mm Up to 1525 mm  
Up to 2475 mm Up to 2475 mm  
Up to 3425 mm Up to 3425 mm  
Up to 4375 mm Up to 4375 mm  
Up to 5325 mm Up to 5325 mm  
   
Up to 7225 mm Up to 7225 mm  
   
   
*Logic Code Combi 38 is capable of 6m ue only
** Logic Code Combi 33 is capable of 8m ue only
*Logic Code Combi 38 is capable of 6m ue only
** Logic Code Combi 33 is capable of 8m ue only
TELESCOPIC FLUE
NON - TELESCOPIC FLUE
206279-10257
2
1
3
206279-1.indd 17 06/01/2011 09:09:56