Checking the System Accuracy
Machine & Bucket Calibration Check for Elevation
Place the bucket on a solid spot in front of the machine with the bucket fully open.
Lock the center tooth on the main working screen by taping on the center tooth on the bucket symbol on the left hand side of the screen.
Mark the spot on the ground where the buckets center is placed.
Set “0” as the elevation on the Control Box.
Raise the bucket approximately 6 ft (2m) higher.
Close the bucket to an approximate floating position.
Place the bucket tip/edge precisely vertical over the marked reference point on the ground.
Measure from the reference spot up to the center of the bucket tip/blade.
Compare the measurement with the reading on the screen.
Being 1/3 inch (1 cm) off is fine.