ifm Programming Manual ecomatmobile BasicController (CR0403) Runtime System V03.02 2015-04-01
ifm function elements ifm function elements for the device CR0403
>
OUTPUT
8078
Unit type = function block (FB)
Unit is contained in the library ifm_CR0403_Vxxyyzz.LIB
Symbol in CODESYS:
>
Description
8079
OUTPUT assigns an operating mode to an output channel (→ data sheet). The FB enables the status
detection on the selected output channel.
The measurement and the output value result from the operating mode indicated via MODE:
• binary output, plus switching (BH) with/without diagnostic function
• binary output, plus switching (BH) with diagnostic function and protection
.
The operating mode should not be changed during operation.
>
Parameters of the inputs
17869
Parameter
Data type
Description
ENABLE
BOOL
TRUE: execute this function element
FALSE: unit is not executed
> Function block inputs are not active
> Function block outputs are not specified
CHANNEL BYTE Number of the output channel (0...11)
0...11 for the outputs OUT0...OUT11
VALUE BOOL TRUE: activate output
FALSE: deactivate output
MODE BYTE Operating mode of the function block:
0 = 0x00 = off
2 = 0x02 = binary output plus switching
15 = 0x0F = binary output plus switching with diagnosis
16 = 0x10 = binary output plus switching with diagnosis
and protection
FILTER BYTE
only for outputs with current feedback:
filter for the measurement on the output:
valid = 0...8 recommended = 4
→ chapter Configure the software filters of the outputs
(→ page 53)
For outputs without current feedback:
FILTER = 0 or: do not set the parameter FILTER!
.
The operating mode should not be changed during operation.