Analogue threshold display DP2200
13
Error signals and diagnosis: Troubleshooting
In the operating mode the input current value is displayed. The scaling depends on the parameter
ScAL ─ scaling of the displayed value (Ò/17).
7.3.1 Representation of the measured current value
21 [mA]3.83.60.30.20 20.5
nPrb UL OL
Input current
Silent
events
3600-21000 μA
Process
data
-32760 3276032764
3.60...21.00 mA
"UL" "OL""nPrb"
IO-Link
2 3
4
1
1: No measured data nPrb: No sensor
2: Input current below the range (-) UL: Process value too low
3: Input current above the range (+) OL: Process value too high
4: Displayed message or value.
The input current is not displayed scaled here.
Hysteresis range