20
9 Parameter setting
During parameter setting the unit remains in the operating mode. It continues
to monitor with the existing parameters until the parameter setting has been
completed.
Exemptions: Changes to the parameters COF (→ 9.4.1), CP1 and CP2 (→ 9.4.7) take effect
immediately.
9.1 Parameter setting in general
3 steps must be taken for each parameter setting:
1
Select parameter
► Press [Mode/Enter] until the
requested parameter is displayed.
If the main menu is protected by an
access code, [Cod0] flashes in the
display.
► Press and hold [Set] until the valid
code no. is displayed.
► Briefly press [Mode/Enter].
When delivered by ifm electronic: no
access restriction.
2
Set parameter value
► Press and hold [Set].
> Current setting value of the
parameter flashes for 5 s.
> After 5 s: setting value is changed:
incrementally by pressing the button
once or continuously by keeping the
button pressed.
Numerical values are incremented continuously. For reducing the value: let the
display move to the maximum setting value. Then the cycle starts again at the
minimum setting value.
3
Acknowledge parameter value
► Briefly press [Mode/Enter].
> The parameter is displayed again.
The new setting value is saved.
Set other parameters
► Start again with step 1.
Finish parameter setting
► Press [Mode/Enter] several times until the current measured value is displayed or wait
for 15 s.
> The unit returns to the operating mode.