10
5 Installation
Before installing and removing the unit: Make sure that no pressure is
applied to the system. Please consider when the system pressure is
displayed in % of the span: "0" does not mean that no pressure is applied
to the system!
The unit must only be installed in a process connection for G1 sealing
cones (e.g. ifm welding adapter, order no. E30013).
If the unit is installed in a 1“ thread without a G1 sealing cone, this will lead
to seal failure. Please use the PI27xx series in these applications.
A guarantee for a long-term stable fitting of the metallic sealing is only valid
for once-only mounting.
Alternatively, adapters with O-ring seal are available that can be used for
frequent inspections.
Installation in a process connection for G1 sealing cones
Slightly grease the thread of
the threaded sleeve (B) using a
lubricating paste which is suitable
and approved for the application.
Insert the unit (A) into the process
connection (C), push the threaded
sleeve towards the internal thread
of the process connection and
lightly screw it in.
Orientate the unit, tighten the
threaded sleeve with a spanner
and ensure that the unit is correctly
oriented while doing so.
Tightening torque 20 Nm.
46
34
A
B
C
Use in hygienic areas to EHEDG
Make sure that the sensor is integrated into the system in accordance with
EHEDG.
See documents of the EHEDG work group.