Chapter 3 Environment description and installation
3-9
3.3.2 MC, MCCB, Fuse and cable specifications.
MCCB/ MC/ Fuse
IMO warranty will not apply under the following condition.
(1) MCCB or fuse is not installed or incorrectly installed or installed with over
capacity, which has resulted in inverter failure.
(2) MC or capacitor or surge absorber is connected in series between inverter
and motor.
iDrive EDX model
###-11/21/43 (-E) ###-43(-E)
020-11/040-11
040-11/040-21
075-21
075-23
150-23 220-23 075/150/220
Fuse
10A
300Vac
16A
300Vac
20A
300Vac
16A/600Vac
MCCB
10A 20A 32A 16A
MC
(from IMO)
MC14-S MC18-S MC32-S
MC18-S
Power terminals
(TM1/TM3)
Cable dimension
2.5mmP
2
P
(13AWG.)
Terminal screw
M4
Cable dimension
4mmP
2
(11AWG)
Terminal screw
M4
Cable dimension
2.5mmP
2
P
(13AWG)
Terminal screw
M4
Control terminals
(TM2)
Cable dimension 0.75mmP
2
P
(18AWG) Terminal screw M3
Use a single fuse for 1-phase input inverter models.
For 3-phase input models, each L1(L)/L2/L3(N) phase must be fused.
Select suitable three-phase squirrel cage induction motor for inverter.
If an inverter drives mote than one motor in parallel, the total operating current should be less
than the inverter rated current.
Suitable thermistor should be installed on each motor.
Do not install capacitor, LC, RC between inverter and motor.