EasyManua.ls Logo

IMO iDrive - Step 3 - Check low speed motor rotation; Step 4 - Check full speed operation

IMO iDrive
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ii
Step 3 - Check low speed motor rotation without load.
Press RUN key. 7-segment display will indicates 00.0 to 05.0. This number is the
frequency output value. The display will now become solid (not blinking) because the
inverter output is on.
Check the operating direction of the motor.
IF the direction of the motor is incorrect:
Press STOP key, turn off the AC power supply. When the power indicator LED is off,
change over motor connections T1 and T2.
Apply the power again, then check the motor direction.
Press STOP key.
Step 4 - Check full speed at 50Hz / 60Hz
Change the frequency with , keys, press DATA/ENT after setting frequency.
Set frequency to 50Hz / 60Hz according to the above.
Press RUN key; check that the motor accelerates smoothly to full speed.
Press STOP key; check that the motor decelerates smoothly to zero speed.
Step 5 - Other settings
For other functions, please refer to iDrive EDX user manual.
Upper frequency limit …………………………... P. 4-9
Lower frequency limit …………………………….P. 4-9
Acceleration time ………………………………… P. 4-10
Deceleration time ………………………………… P. 4-10
Control mode (Vector, V/F) ………………………P. 4-10
Motor rated current ………………………………P. 4-13