User Manual PROFview XL 4 The PROFview XL Application Software
This measurement simplifies the station-related displaying and evaluation of the data sent along the
PROFIBUS through the use of an oscilloscope, since triggering is only performed exactly to one station ad-
dress. The Sections 2.3.4 "Connecting the PROFIBUS Tester to a storage oscilloscope" and 3.2.6 "Trigger-
ing to a station address" describe in detail how the PBT can be used in conjunction with an oscilloscope.
4.7.2 Setting and measuring
The requirements for this measurement are:
The PBT must be connected both to a PC and to the PROFIBUS plant (bus status LED = green/yellow)
The correct baud rate must be selected.
The master simulator must be activated if necessary (only required when performing a measurement on
an idle plant - bus status LED = yellow/red, differential voltage > 0.1 V)
The correct measuring point must be selected.
At least one station must exist in the station list and must be marked as "to be measured".
PROFview XL 23