Write Commands AUTO-TILT
Command Returns Description
LD iii INT AT iii Switch AUTO-TILT off:
LD 0 INT AT
Warning:
This disables AUTO-DISTANCE as well
Switch AUTO-TILT on:
LD 1 INT AT
Warning:
AUTO-TILT is only applied if the height-axis is moved
LD iii INT ATMH iii Switch modus between Mast-Height and Antenna-Reference-Height
Set to Antenna-Reference-Height (default)
LD 0 INT ATMH
Warning:
Only active if AUTO-TILT is switch on.
Set to Mast-Height
LD 1 INT ATMH
LD ppp CM DZ
ppp
Object-Setup: Object-Height
Use this to set the Object-Height in cm.
LD ppp CM ARP
ppp
Mast-Setup: Antenna-Reference-Point (ARP)
Use this to set the Antenna-Reference-Length, the distance from the
antenna-pivot-point to the antenna-reference-point in cm.
LD ppp CM DYMD
ppp
Mast-Setup distance (SETUP M-DISTANCE)
Sets distance between Antenna-Reference-Point and Object in cm.
Attention:
With regards to the SETUP M-DISTANCE please refer to the device-
manual on how to properly setup the mast.
© innco systems GmbH Schwarzenfeld/Germany
Erlenweg 12, 92521 Schwarzenfeld/Germany Phone: +49 9435 301659 0 Fax: +49 9435 301659 99
Email: info@inncosystems.com