Function
code
Name LED display Set range
Minim-
um unit
Factory
default
value
Modication
description
F8-14
Setup
frequency
lower than
frequency
lower limit
action
Frequency
lower limit
action
0: Run with frequency lower limit
1: Stop
2: Zero speed operation
1 0
☆
F8-15 Droop control Droop control 0.00Hz
~
10.00Hz 0.01Hz 0.00Hz
☆
F8-16
Over
modulation
enabled
Over
modulation
enabled
0: Over modulation inactive
1: Over modulation active
1 1
☆
F8-17
Set running
time
Set running
time
0h
~
65535h 1h 65535h
☆
F8-18
Start
protection
selection
Start
protection
selection
0: No protection
1: Protection
1 0
☆
F8-19
Frequency
detection
value
(FDTlevel)
FDT level 0.00 ~ maximum frequency 0.01Hz 50.00Hz
☆
F8-20
Frequency
detection
hysteresis
(FDT-
hysteresis)
FDT
hysteresis
0.0% ~ 100.0%(FDT level) 0.1% 5.0%
☆
F8-21
Frequency
arrival
detection
width
Frequency
arrival width
0.0 ~ 100.0%
(maximum frequency)
0.1% 0.0%
☆
F8-22
Earth short
circuit
protection
detection
upon power-
on
Earth short
circuit
protection
detection upon
power-on
0: Inactive
1: Active
1 1
☆
F8-23
Running time
to action
selection
Running time
to action
selection
0: Continue running
1: Stop
1 0
★
Group F9 Fault and Protection
F9-00
Motor
overload
protection
selection
Overload
protection
selection
0: Inactive
1: Active
1 1
☆