Function Parameter Table MD320/MD320N User Manual
84
Function
code
Name LED display Set range
Minim-
um unit
Factory
default
value
Modication
description
F9-01
Motor
overload
protection
gain
Overload
protection
coefcient
0.20
10.00 0.01 1.00
F9-02
Motor
overload
pre-warning
coefcient
Overload
pre-warning
coefcient
50%
100% 1% 80%
F9-03
Stall gain over
voltage
Stall gain over
voltage
0(no stall over voltage) to 100 1 0
F9-04
Stall
protection
voltage over
voltage
Stall point over
voltage
120%
150% 1% 130%
F9-05
Stall gain over
current
Stall gain over
current
0
100 1 20
F9-06
Stall
protection
current over
current
Stall point over
current
100%
200% 1% 150%
F9-07
Transient
stop/ non-stop
function
Transient
stop/ non-stop
function
0: Inactive
1: Active
1 0
F9-08
Transient
stop/ non-stop
frequency
falling rate
Transient
stop/ non-
stop frequency
falling rate
0.00Hz/s ~ maximum frequency/s
0.01Hz/
s
10.00Hz/s
F9-09
Fault auto
reset times
Fault auto
reset times
0
3 1 0
F9-10
T/A-T/B-T/
C
Faulty
rely action
selection
during the
fault auto
reset
0:No action
1: Action
1 0
F9-11
Fault auto
reset interval
Fault auto
reset interval
0.1s
100.0s 0.1s 1
0s
F9-12
Input phase-
failure
protection
selection
Input phase-
failure
selection
0: Inactive
1: Active
1 1

Table of Contents