Common Parameter Settings
‑62‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
F0‑56 0xF038 Jogging frequency
1 source
0: F0‑57
2: AI1
5: Pulse reference
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication
10: Potentiometer MD‑BP‑M
Others: F connector
0 ‑ Real time
F0‑57 0xF039 Digital setting of
jogging frequency 1
‑50.00 Hz to 50.00 Hz 2.00 Hz Real time
F0‑58 0xF03A Jogging frequency
2 source
0: F0‑59
2: AI1
5: Pulse reference
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication
10: Potentiometer MD‑BP‑M
Others: F connector
0 ‑ Real time
F0‑59 0xF03B Digital setting of
jogging frequency 2
‑50.00 Hz to 50.00 Hz ‑2.00 Hz Real time
F0‑62 0xF03E Jogging ramp
source
0: Normal running ramp time
1: Jogging ramp time
0 ‑ Real time
F0‑63 0xF03F Ramp acceleration
time of jogging
0.00s to 650.00s 20.00 s Real time
F0‑64 0xF040 Ramp deceleration
time of jogging
0.00s to 650.00s 20.00 s Real time
F1‑00 0xF100 Motor type 0: Common asynchronous motor 0 ‑ Unchangea
ble
F1‑01 0xF101 Rated motor power 0.1 kW to 1000.0 kW 3.7 kW At stop
F1‑03 0xF103 Rated motor
voltage
1 V to 2000 V 380 V At stop
F1‑04 0xF104 Rated motor
current
0.01 A to 655.35 A 9.00 A At stop
F1‑06 0xF106 Rated motor
frequency
0.01 Hz to 599.00 Hz 50.00 Hz At stop
F1‑07 0xF107 Rated motor speed 1 RPM to 65535 RPM 1460 RPM At stop
F1‑10 0xF10A Maximum motor
frequency
C4‑06 to 599.00 Hz 50.00 Hz At stop
F1‑11 0xF10B Minimum motor
frequency
0.00 Hz to C4‑10 0.00 Hz At stop
F1‑20 0xF114 Stator resistance 0.001 Ω to 65.535 Ω 1.204 Ω Real time