Electrical Design
‑82‑
Figure 3‑19 STP
Table 3–33 Recommended cable specifications for the control circuit
Category
Terminal Type Recommend
ed IEC Cable
Specifications
(mm
2
)
Recommend
ed NEC Cable
Specifications
(AWG)
Recommended Lug
Specifications
Power supply
unit and
optional
expansion
card
Control signal
terminal
0.5 22‑20 IEC:
0.5 mm
2
(E0512)
0.75 mm
2
(E7512)
1 mm
2
(E1012)
1.5 mm
2
(E1512)
NEC:
22 AWG (E0512)
20 AWG (E0512)
18 AWG (E1012)
16 AWG (E1512)
For details about the
lug specifications, see
"
3.1.3 Lug Selection
"
on
page 49Lug Selection
.
24 V input
terminal
0.5‑1.5 22‑16
Relay terminal
0.5‑1.5 22‑16
Drive unit
STO terminal
(optional)
0.5 22‑20
Wiring Requirements for the I/O Signal Cables
● I/O signals include analog input (AI), analog output (AO), digital input (DI), digital
output (DO) and relay output signals. Before wiring the I/O terminals, disconnect
the main power supply and ensure that the danger indicator of the AC drive is off.
● To avoid interference on the I/O signals, separate the I/O signal cables at least 30
cm from the main circuit cables (three‑phase R/S/T and U/V/W, or single‑phase L1/
L2) and other power cables (or power lines).
● To avoid malfunction of the AC drive and equipment, separate the cable
connecting the relay output terminal from other I/O signal cables by more than 30
cm.