Electrical Design
46
Terminal Arrangement of the Filter Unit
Table 3–6 Terminal description of the filter unit
No.
Terminal Name
Function Description
1
R/L1, S, T/L2 input terminals Used for power input.
2
Input M4 grounding screw Used for input grounding.
3
R'/L1', S', T'/L2' output
terminals
Used to connect the power
supply unit.
4
Output M4 grounding screw Used for output grounding.
5
Optional EMC screw Used for EMC grounding
(optional).
3.1.2 Main Circuit Wiring Requirements
Main Circuit Wiring Requirements
Terminals BR and (+) are used to connect options. Do not connect them to the AC
power supply.
The wire for the braking unit cannot exceed 10 m. Use the twisted pair wire or
tight pair wires for parallel connection.
Do not connect the braking resistor directly to the DC bus. Otherwise, the device
may be damaged and even a fire may occur.
The specifications and installation method of main circuit cables must comply
with local regulations and related IEC requirements. Use copper conductors of a
proper size as main circuit cables according to the recommended values of main
circuit cable selection in this user guide.
To protect the main circuit, separate it from the possible contact surface and
provide covers as required.