Parameter Communication Address
‑9‑
Para. Address
Description
Control command
input to AC drive
(write‑only)
7311H
0: Stop by a stop method set in F6‑10 (Stop mode)
1: Forward run
2: Reverse run
3: Forward jog
4: Reverse jog
5. Coast to stop
6: Decelerate to stop
7: Fault reset
Read AC drive state
1
703DH
1: Forward run
2: Reverse run
3: Stop
4: Auto‑tuning
5: Fault
Read AC drive state
2
7044H
Bit0: Running status
Bit1: Forward/Reverse state
Bit2: Whether a fault occurs
Bit3: Whether the output frequency reaches the
frequency reference
Bit4: Communication normal flag
Bit5 to Bit7: Reserved
Bit8 to Bit15: Fault code
Parameter locking
password check
1F00H
Parameter locking password check: If the actual
password value is returned, password check
succeeds. (If no password is set, namely, the
password is 0, 0000H is returned.)