Parameter Communication Address
‑15‑
No station number conflict will occur in this mode. Station number conflicts
between cascaded AC drives cannot be detected.
● Manual assign mode
An alarm is triggered in the case of duplicate station numbers in one group.
Station number conflicts between cascaded AC drives cannot be detected.
1.4.2 Parameters
The following parameters are all set in the power supply unit. You do not need to set
any parameters in the drive unit.
Table 1–2 Parameters
Para. Name Value
Range
Meaning Attribute Description
Fd‑18 Number of the power supply
unit
1 to 15 RW The number of each
group of AC drive.
The system can
automatically assign
station numbers for a
maximum of 15 groups.
15 x 16 = 240. The value
cannot exceed 255.
Fd‑39 Station number setting mode 0 to 1 0: Auto
1: Manual
RW Specifies the mode of
station number
assignment.
Fd‑40 Manual setting of power
supply unit station number
0 and 1 to
127
RW The station number of
the power supply unit
that is manually set.
Fd‑41 Manual setting of drive unit 1
station number
0 and 1 to
127
RW
Fd‑42 Manual setting of drive unit 2
station number
0 and 1 to
127
RW
Fd‑43 Manual setting of drive unit 3
station number
0 and 1 to
127
RW
Fd‑44 Manual setting of drive unit 4
station number
0 and 1 to
127
RW
Fd‑45 Manual setting of drive unit 5
station number
0 and 1 to
127
RW
Fd‑46 Manual setting of drive unit 6
station number
0 and 1 to
127
RW
Fd‑47 Manual setting of drive unit 7
station number
0 and 1 to
127
RW
Fd‑48 Manual setting of drive unit 8
station number
0 and 1 to
127
RW
Note: When Fd‑39 is set to 1, Fd‑40 to Fd‑48 are valid.