6 Parameter Description
-
213
-
F6-11 Elevator function selection
Bit Function Description Default
Bit1
Disabling returning
the car position is disabled.
0
Bit2
Canceling auto
sequential arrange
addresses to be
displayed
displayed are automatically arranged in
the ascending order. This bit is used to
cancel this function.
0
Bit5
Current detection
valid at startup for
synchronous motor
The controller performs output current
detection when the synchronous motor
is started up. If the current is abnormal,
the output will be locked and the
running will be forbidden.
0
Bit6
Reversing MCB lamp
output
After this function is enabled, the MCB
lamp output logic is reversed.
0
Bit7
Door open valid at
non-door zone in the
inspection state
In the inspection state, you can open/
close the door by pressing the door
open/close button at the non-door
zone.
0
Bit8
Door open and close
once after inspection
turned to normal
The elevator door opens and closes
time inspection to normal running.
1
Bit10
Buzzer not tweet upon
re-leveling
The buzzer inside the car does not
tweet upon re-leveling.
0
Bit11
function
The controller cannot perform shaft-
500 mm. After this function is enabled,
shaft-tuning can be performed
normally.
0
Bit12
Automatic reset of
faults
The controller automatically resets the
faults once every hour.
0
Bit13 E53 fault auto reset
When E53 is reported, if the conditions
of door open limit valid and door lock
resets E53 automatically. A maximum
of three times of auto reset is allowed.
1
Bit14
Up slow-down not
reset for super short
If this function is enabled, the up slow-
display. The down slow-down 1 signal
only when the customized super short
0