6 Parameter Description
-
222
-
Function
Code
Name Setting Range Default Unit Property
F6-45
Emergency evacuation
function selection
0 to 65535 0 -
F6-45 is used to select the emergency evacuation-related elevator functions. Each bit
󶍾
this bit is enabled; if this bit is set to 0, the function is disabled.
󶍿
in F6-49.
󶍿
󶍾
F6-45 Emergency evacuation function selection
Bit Function Description Default
Bit0
Direction
determine
mode
0
Automatically
calculating the
direction
(The elevator
runs in heavy-
load direction.
The no-load-
cell function
must be
enabled.)
0
Direction
of nearest
landing
󶍿
1
Load direction
determining
(The elevator
runs in heavy-
load direction.
The load-cell
function must be
enabled.)
0
Bit1 0 1 0 0
Bit2
Stop at the
󶍿
During evacuation running, the elevator arrives at the
󶍿
󶍿
󶍿
0
Bit3
Single leveling
door open
During evacuation running, the elevator arrives at the
󶍿
elevator decelerates to stop.
0
Bit4
Startup
compensation
Startup torque compensation valid in emergency
evacuation running
0
Bit5
to
Bit7
Reserved - 0
Bit8
Emergency
evacuation
running time
protection
󶍿
50s emergency evacuation running time, E33 is reported.
This function is invalid when the function of switching over
shorting stator braking mode to controller drive is used.
0
Bit9 Reserved - 0
Bit10
Emergency
buzzer output
The buzzer output is active during UPS emergency
evacuation running.
0
Bit11 Reserved - 0
Bit12
Shorting stator
braking mode
switched over
to controller
drive
If the speed is still lower than the value set in F6-48 after
the elevator is in shorting stator braking mode for 10s, the
shorting stator braking mode is switched over to controller
drive.
0