EasyManuals Logo

Intec Controls MSR PolyGard 2 DGC6 User Manual

Default Icon
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | GAGC06_E_0516 | USA 200303 | Page 7 of 41
DGC6 – UserManual
3.3 Code Levels
According to the regulations of all national and international standards for gas warning systems, all inputs and changes
are protected by a four-digit numeric code (= password) against unauthorized intervention. The menu windows for
status messages and measuring values are visible without entering a code.
The cancellation of a password level takes place when no buttons are pushed within 15 minutes.
The code levels are classied in order of priority: Priority 1 has top priority.
Priority 1: Upper Level (password 9001 – not changeable)
Code level priority 1 is intended for the service technician of the installer to change parameters and set-points. This
password allows working on all settings. For opening the parameter menus you must rst activate the service mode 
after code entry.
Priority 2: Lower Level (password 1234 – not changeable)
Code level priority 2 allows the operator:
- to acknowledge faults
- to set date and time
-  to congure and to operate the data logger option, after activation of the operation mode “Service Mode”
- to read all parameters
- to manually operate test

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Intec Controls MSR PolyGard 2 DGC6 and is the answer not in the manual?

Intec Controls MSR PolyGard 2 DGC6 Specifications

General IconGeneral
BrandIntec Controls
ModelMSR PolyGard 2 DGC6
CategoryController
LanguageEnglish