DGC6 – UserManual
4.1 Fault Management
The integrated fault management records the rst 100 faults with date and time stamps in the menu “System Errors”. 
Additionally a record of the faults occurs in the “History Error”, which can only be read and reset by the service
technician.
A pending fault activates the fault indication relay. The yellow LED (Fault) starts to ash; the fault is displayed in plain 
text with date and time in the starting menu.
In case of the fault of a connected sensor the alarms dened in the menu “SP Parameter” are activated in addition.
4.1.1 Acknowledge a Fault
According to the directives for gas measuring, accumulated errors are allowed to be acknowledged automatically. The
automatic acknowledgment of a fault is only possible after having removed the cause!
4.1.2 History Error
The menu “History Error” in the main menu “System Errors” can only be opened via the code level priority 1.
In the error memory, the rst 100 faults that have occurred and have already been acknowledged in the menu “System 
Error” are listed for the service technician in non volatile memory.
Attention:
This memory should always be read during maintenance, relevant faults should be tracked and entered in the service
logbook, and nally the memory should be emptied.
Acknowledge the fault message?
Fault message acknowledged.
Example: Communication error DP01 Error
Select menu “History Error”
Fault acknowledged
DP 1 Error
Cancelled
DP 1 Error
Reset?
DP 1 Error
05.02 10:38
Hi󰀬ory Error